Electrical Requirements
The chart
below shows the recommended electrical specifications for each kiln model.
If you are uncertain about your existing power, have it checked by an electrician.
If you are installing a new kiln, have the electrician follow this guide.
Electrical requirements for Skutt Automatic Kilns
| Model |
Voltage |
Amp |
Watts |
Wire Size* |
Breaker Size |
Max Temp |
NEMA Receptacle |
 |
| GM10F |
115 |
15 |
1725 |
10 |
20 |
1800 |
5-15 |
| GM814 |
240 |
27.8 |
6660 |
8 |
40 |
1800 |
6-50 |
| GM814 |
208 |
32 |
6656 |
8 |
40 |
1800 |
6-50 |
| GM1014 |
240 |
34 |
8140 |
6 |
50 |
1800 |
6-50 |
| GM1014 |
208 |
39.1 |
8140 |
6 |
50 |
1800 |
6-50 |
| GM1414 |
240 |
34.7 |
8320 |
6 |
50 |
1800 |
6-50 |
| GM1414 |
208 |
40 |
8320 |
6 |
50 |
1800 |
6-50 |
| GM1414 3ph |
240 |
20 |
8320 |
10 |
30 |
1800 |
15-50 |
| GM1414 3ph |
208 |
23.1 |
8320 |
10 |
30 |
1800 |
15-50 |
| GM818 |
240 |
27.8 |
6660 |
8 |
40 |
1800 |
6-50 |
| GM818 |
208 |
26.7 |
5550 |
8 |
40 |
1800 |
6-50 |
| GM1018 |
208 |
40 |
8320 |
6 |
50 |
1800 |
6-50 |
| GM1027 |
240 |
48 |
11520 |
6 |
60 |
1800 |
6-50 |
| GM1027 |
208 |
48 |
9980 |
6 |
60 |
1800 |
6-50 |
| GM1027 3ph |
240 |
29.3 |
11520 |
8 |
40 |
1800 |
15-50 |
| GM1027 3ph |
208 |
31.7 |
11000 |
8 |
40 |
1800 |
15-50 |
| GM1227 |
240 |
48 |
11520 |
6 |
60 |
1800 |
6-50 |
| GM1227 |
208 |
48 |
9980 |
6 |
60 |
1800 |
6-50 |
| GM1227 3ph |
240 |
29.3 |
11520 |
8 |
40 |
1800 |
15-50 |
| GM1227 3ph |
208 |
31.7 |
11000 |
8 |
40 |
1800 |
15-50 |
| GM22CS |
240 |
31 |
7450 |
6 |
40 |
1800 |
6-50 |
| GM22CS |
208 |
35.8 |
7450 |
6 |
40 |
1800 |
6-50 |
| GM22CS 3ph |
240 |
17.9 |
7450 |
10 |
30 |
1800 |
15-50 |
| GM22CS 3ph |
208 |
20.7 |
7450 |
10 |
30 |
1800 |
15-50 |
All Skutt
kilns are equipped with a type K thermocouple.
*For each additional 50 feet use heavier wire, numerically two numbers
lowerfor example, instead of #10, use #8. If you anticipate installing
any larger kiln in the future, use the heavier wire. |
|